Warrick Conductivity Controls Sensitivity vs. Maximum Probe Wire Distances 

Sensitivity vs. Maximum Probe Wire Distances - in feet*

Notes:

  1. DC on probe circuit-maximum distance between control and probe is limited to the total resistance of the wire and liquid.
  2. Total resistance must not exceed the sensitivity of the control.
  3. On controls directly connected to floats rather than probes, maximum distance is limited only to the total resistance of the wire.
  4. AC probe circuit has greater restrictions on maximum distance.

*Based on type MTW or THHN #14 or #16 AWG wire. Other wire size and sensing medium may reduce overall maximum distance.

 

Ohms Series
16, 16D, 16M, 16DM, 16VM
Series
17
Series
27
Series
47
Series
67
Series
26, 26M
Series
19MR
Series
DF
3,000 -- -- 4000 -- -- -- -- --
3,300 -- 5000 -- -- -- -- -- --
4,700 10000 3500 -- -- 4000 900 -- 900
10000 5700 1750 900 -- 2400 600 -- 600
11,000 -- -- -- -- -- -- 5500 --
19,000 -- -- -- -- -- -- 3000 --
22,000 -- 1000 -- -- -- -- -- --
26,000 2200 -- -- 1500 1200 250 -- 250
47,000 -- 500 -- -- -- -- -- --
50,000 1075 -- -- 900 600 -- -- --
100,000 570 250 75 -- -- -- -- --
470,000 270 -- -- -- -- -- -- --
1,000,000 38 -- -- 400 300 -- -- --

 

For Ohms 3,000,000 & 5,500,000, Contact Factory for more information.